Technical selection/Chiller Selection Guide
Refrigeration Equipment Selection Guide

Chiller Selection Guide

A detailed guide to chiller types, cooling capacity calculation, selection parameters and purchasing checks.

Chiller overview

Chillers are core equipment for industrial cooling and process temperature reduction. Selection essentials:Determine cooling capacity → choose compressor type → confirm condensing method → check site conditions。

Screw chiller
100–2000 kW+, mainstream industrial
Reciprocating chiller
50–300 kW, small capacity
Scroll chiller
10–100 kW, small capacity
Low-temperature brine unit
Below −40 °C, chilled brine
Air-cooled chiller
No cooling tower required, outdoor installation

Chiller type comparison

TypeCompressorCapacity rangeFeaturesUse cases
Screw chillerScrew100~2000kW+High efficiency, stable operation, low noiseLarge capacity, mainstream industrial
Reciprocating chillerReciprocating50~300kWSimple structure, low costSmall capacity, retrofit projects
Scroll chillerScroll10~100kWHigh efficiency, low noiseSmall capacity, cleanrooms
Low-temperature brine unitScrew/reciprocatingDepending on dutyCan produce brine below −40 °CChemical processes, low-temperature reactions
Air-cooled chillerScrew/scroll50~500kWNo cooling tower required, outdoor installationWater scarcity, small-medium capacity

Cooling capacity calculation

Formula: capacity (kW) = flow (m³/h) × ΔT × 1.163

Example: chilled water 10 m³/h, inlet 12 °C, outlet 7 °C, ΔT 5 °C

Capacity = 10 × 5 × 1.163 = 58.15 kW → select a 65 kW unit (10–15% margin)

Note:Allow a 10–15% capacity margin. Confirm whether duty is continuous or intermittent; for sustained load choose one size larger.

Parameters that must be confirmed

Required parameters

  • - Chilled water outlet temperature (e.g. 7 °C)
  • - Chilled water inlet temperature (e.g. 12 °C)
  • - Chilled water flow (m³/h)
  • - Cooling water inlet temperature (e.g. 32 °C)
  • - Condenser type (air-cooled/water-cooled)
  • - Voltage (380 V/10 kV)

Points to note

  • - Allow a 10–15% capacity margin
  • - Confirm continuous or intermittent operation
  • - Confirm whether split loads are needed
  • - Confirm maximum ambient temperature
  • - Confirm water quality (softened/industrial/purified)

Selection checklist

Selection confirmation

  • 1.Confirm capacity requirement and outlet temperature
  • 2.Confirm compressor brand and running hours
  • 3.Check condenser cleanliness and heat transfer
  • 4.Check electrical control system and PLC
  • 5.Request a cooling capacity test report
  • 6.Check refrigerant oil level and colour
  • 7.Power up and test-run to confirm normal noise and vibration

Equipment condition check

  • - Request a powered test-run video or an on-site trial run
  • - Inspect wear of main components and operating condition
  • - Confirm all documentation and conformity certificates are complete